Level Switch

CRF312 Series RF Admittance Level Switch

crf312-rf-admittance-level-switch-800
RF admittance point level detection for liquids, solids, powders and slurries.

Application Scenario

The RETTAR CRF312 Series RF admittance level switch provides high and low point level detection for tanks and silos containing liquids, solids, powders or slurries. Its sensing probe and the container wall form a capacitor. As the material level changes around the probe, the difference in dielectric properties between air and the material changes the measured capacitance. The instrument produces a switching signal when the configured threshold is reached. A digital menu and graphical display support parameter setting and status checks. Bluetooth commissioning allows remote adjustment, and integrated temperature compensation helps correct temperature effects on the capacitance signal. Relay switching output provides an interface for level alarms and process control.

Advantage

Digital Parameter Setting. Use menu-based commissioning to set the instrument without mechanical adjustment knobs.
Graphical Level Status. Check silo status, measured values and switching thresholds on the display.
AC/DC Supply. Options AC and DC compatibility supports installation in different plant power systems.
Bluetooth Adjustment. Commission the instrument remotely to reduce the need to reach high mounting positions.
Integrated Compensation. Temperature compensation helps correct the effect of temperature changes on capacitance.
Relay Output. Interface A 2-channel switching configuration with DPDT relay output connects to the plant control system.

Specifications

Parameter Type Specific Value
Measured Medium Solids, liquids, powders and slurries
Dielectric Constant ε ≥ 1.6
Operating Voltage 15–230 VAC, 50/60 Hz, ±15%; 18–320 VDC, ±15%
Power Consumption < 1 W
Output 2-channel switching; DPDT relay output (220 VAC / 5 A; 30 VDC / 5 A)
Adjustable Delay 0–999 s
Response Time 1 s
Sensitivity 0.3 pF
Operating Pressure −0.1 to 64 bar
Sensor Temperature −50 to +200 °C
Electronic Unit Temperature −40 to +80 °C
Protection Rating IP67
Electrical Entry M20 × 1.5 / 1/2″ NPT
Process Connection Thread: G3/4 or 3/4″ NPT and larger; flange: DN50 or 2″ and larger
Process Seal Fluoroelastomer
Wetted Material Options SS304 + PTFE; SS316L + PTFE; SS304 + FEP; SS316L + FEP

Access detailed technical specifications by down loading our datasheet.

Download

Get all the technical details you need by downloading our product specs.